In a two-wattmeter method for 3-phase power measurement, one wattmeter reads zero when the load power factor angle is:

A60 degrees (cos phi = 0.5)
B0 degrees (cos phi = 1.0)
C90 degrees (cos phi = 0.0)
D30 degrees (cos phi = 0.866)

Explanation

When phase angle phi = 60° (power factor = 0.5), one wattmeter reads W2 = V_L * I_L * cos(30° + 60°) = cos(90°) = 0.

Submitted by: mcqstutor Team More Electrical Engineering MCQs →